- Product details
- Specifications
-
Applicable to the detection of water flooding in important places such as the base station of the computer room and the warehouse;
New patent design, with HW-1018 water detection line use;
Good isolation: input, output and power completely isolated, safe and reliable;
Range optional: Check out range can be divided into four ranges, through the knob switch selection;
Advanced technology: multifunctional detection mode, probe no electrical corrosion phenomenon, full thread detection;
Safe and reliable: automatic detection of line failure.
-
Parameters of flood adapter:
Power supply: 12-60VDC;
Range of sensitivity
Gear 1:0-250kω;
Tap 2:0-600kω; Gear 3:0-5mω;
Gear 4:0 -- 50MΩ; (High sensitive gear, can alarm when encountering very little water)
Output form: dry contact, output normally open, normally closed when water detection can be jumper choice, factory default is normally open.
Short circuit impedance <50Ω, load voltage < 60V, load current < 30mA;
Warning: The load should not exceed the maximum value, otherwise the adapter will be damaged.
Static current: <60mA; Alarm current: <90mA;
Environment: -10~55℃, 10~98%RH; Size: 95x 37x30mm;
Weight: 85g;
Parameters of water detection line:
Length optional: 2m, 10m, 20m, 30m, other customized)
Weight: 1kg (10m length);
Probe density: full thread;
Width: 12mm;
Thickness: 5.5mm.
The data listed in this information is for reference only, specific product data to ship with product descriptions shall prevail, subject to change without notice